NCIN Device (RCD)
Speifications
Rated Voltage(Un) | 2Pole:230V AC 4Pole:400V AC |
Rated Current(In) | 25,40,63A |
Rated Residual Operating Current(IΔn) | 30,100,300,500mA |
Rated Residual Non-operating Current(IΔno) | 0.5IΔn |
Rated Current off-time | ≤0.1S |
Min Value of Rated Operating and Breaking Capacity(Im) | 1kA |
Rated Conditional Short-circuit Current(Inc) | In=25,40A Inc=1500A In=63A Inc=3000A |
Installation | On symmetrical DIN rail |
Endurance(times) | 4000 |
Application
The residual current device(RCD) NCIN is in conformity with the standards of IEC1008, VDE 0664, CEE27 and BS4293.
It can cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunk line. Thus it is suitable to avoid the shock hazard and fire caused by earth leakage.
NCIN RCD is mainly suitable for using in varieties of plants, enterprises, buildings. Constructions, commerce, hotels and families. It can be used in circuit up to single phase 240V, three phase 415V, 50 or 60Hz.